Two leakage measurements appear in equipment standards, and they are frequently treated as one. They measure different currents through different paths, against different limits.
The two paths
Touch current flows from an accessible conductive part, through a person, to earth. It is measured with the part disconnected from earth so that the current that would flow through a person is the current measured.
Protective conductor current flows from the live parts, through the insulation or the filter, to the protective conductor. It is measured in the earth conductor while the equipment remains earthed.
The distinction matters because the paths are not the same and the limits are not the same. A product with a large Y-capacitor to earth has a high protective conductor current and a low touch current — because the capacitor shunts the current to earth before it can reach a person.
| Measurement | Earth state | What it predicts |
|---|---|---|
| touch current | part isolated | shock risk to a person |
| protective conductor | earthed | earth path loading, RCD tripping |
Why the second one matters
A protective conductor current that is high has three consequences, none of which show up in a touch current test:
It can trip a residual current device. A 30 mA RCD protecting several products will trip if their combined earth leakage approaches the threshold. Users experience nuisance tripping and blame the installation.
It loads the earth conductor. The conductor is sized for fault current, not continuous current, and a continuous leakage raises its temperature.
It indicates the earth path is carrying current in normal operation, which means the equipment is not truly isolated from earth by its insulation.
Where the current comes from
Three sources dominate:
Y-capacitors in the EMI filter. Their whole purpose is to shunt common-mode noise to earth, and they shunt 50 Hz current too. Two 2.2 nF capacitors at 230 V produce roughly 0.7 mA.
Insulation capacitance in motors and transformers. Small per unit, but a large machine has a lot of it.
Actual insulation resistance. Usually negligible, unless the insulation is damp or degraded.
The measurement
The instrument measures the current in the protective conductor. It must not disturb the earth connection during the measurement, which is why the measurement is made with a current transformer or a low-impedance shunt rather than by breaking the circuit.
Two practical requirements:
Measure at the rated voltage and frequency. The current is largely capacitive, so it is proportional to frequency — a 60 Hz measurement is 20 percent higher than at 50 Hz.
Measure with the equipment operating normally. A product in standby may have its filter disconnected, and the reading will not represent service conditions.
The limits
Limits are set per equipment category and are generally more generous than touch current limits, because the current is going where it should go. But they are not unlimited: a product with a leakage of several milliamps requires a permanent connection rather than a plug, in many standards.
That is the practical consequence worth knowing: the limit is not only a number to pass, it determines how the product may be connected.
What to record
Current, voltage and frequency at measurement, equipment state (operating or standby), and which conductor was measured. Four items. Without the frequency, two readings cannot be compared.